Windrose Compute
AI Compute in a 20 ft Container, Running on Truck Batteries
A Data Hall in a Shipping Container
Compute puts four NVIDIA GB300 NVL72 racks — 288 Blackwell Ultra GPUs — into one 20 ft high-cube container, with six unmodified Windrose E700 battery packs on board. The packs carry the box for 1.4 hours at full load; with one Windrose Power container docked, for 3.2 hours. The racks are cooled by warm water, so there is no chiller anywhere in the loop.
Same pack as the E700
6 × 176 kWh LFP on board
No chiller
45 °C warm-water cooling
Docks to Windrose Power
Fed by Windrose Power
Racks, Batteries, Power and Cooling
Four NVL72 racks
Side by side and turned 90° so the fronts face one cold aisle. Each rack holds 18 compute trays (2 Grace CPUs + 4 Blackwell Ultra GPUs each) and 9 NVLink switch trays, 132–142 kW nominal and 155 kW peak.
Sealed battery bay
Six E700 LFP packs, 1,051 kWh, behind an EI 60 fire-rated bulkhead. At full load each pack runs at 0.65C. The bay has its own 15 kW cooling, off-gas detection, aerosol suppression and roof deflagration vents.
Power conversion
A 2 × 500 kW bidirectional PCS turns the 595–869 V pack bus into 415 V three-phase. A 1,250 A overhead busway feeds each rack’s power shelves.
Warm-water cooling
Two 700 kW coolant distribution units (N+1) feed the racks at 45 °C and take them back at 57 °C. A roof dry cooler with four EC fans rejects the heat. Two 30 kW room-air units handle what the cold plates do not catch.
Full Technical Specifications
| Category | Item | Parameters |
|---|---|---|
| Compute | Racks | 4 × NVIDIA GB300 NVL72 |
| GPUs | 288 Blackwell Ultra (72 per rack, one NVLink domain per rack) | |
| IT load | 528–620 kW (155 kW peak per rack) | |
| Facility load | 671 kW · PUE 1.08 | |
| Energy | On-board battery | 6 × Windrose E700 LFP pack, 1,051 kWh |
| Runtime at full load | 1.4 h on its own packs · 3.2 h with one Windrose Power | |
| Power | PCS | 2 × 500 kW bidirectional, 415 V three-phase, 98.2 % peak efficiency |
| Busway | 1,250 A plug-in, one tap-off per rack | |
| Cooling | Coolant distribution | 2 × 700 kW CDU, N+1 |
| Rack loop | 45 °C supply / 57 °C return, no chiller | |
| Heat rejection | Roof dry cooler, 4 × EC fans | |
| Safety | Battery bay | EI 60 bulkhead, gas detection, aerosol suppression, deflagration vents |
| Rack zone | Clean-agent (Novec 1230) suppression, aspirating smoke detection | |
| Container | Size | 20 ft high-cube: 6,058 × 2,438 × 2,896 mm |
Planning AI capacity at a site?
Contact us — we'll size Compute and Power for your racks and site.